Table 82: Input pressure supervision parameters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.13.9.6
Supervision
Unit Maximum
Value
-99999.99 99999.99
P3.13.9.3
10.00
1690
P3.13.9.7
Supervision
Alarm Level
P3.13.9.5 P3.13.9.6
P3.13.9.3
Varies
1691
P3.13.9.8
Supervision
Fault Level
P3.13.9.5 P3.13.9.7
P3.13.9.3
0.10
1692
P3.13.9.9
Supervision
Fault Delay
0.00
60.00
s
5.00
1693
P3.13.9.10
PID Setpoint
Reduction
0.0
100.0
%
10.0
1694
V3.13.9.11
Input Pressure
P3.13.9.5 P3.13.9.6
P3.13.9.3
Varies
1695
This monitoring value
shows the actual value
of the pump input
pressure.
Table 83: Sleep - no demand detected
Index
Parameter
Min
Max
Unit
Defaul
t
ID
Description
P3.13.10.1
Sleep No
Demand Detec-
tion Enable
0
1
0
1649
0 = No
1 = Yes
P3.13.10.2
SNDD Error Hys-
teresis
0
99999.9
P3.13.1.4
0.5
1658
P3.13.10.3
SNDD Frequency
Hysteresis
0.00
P3.3.1.2
Hz
3.00
1663
P3.13.10.4
SNDD Supervi-
sion Time
0
600
s
120
1668
P3.13.10.5
SNDD Actual Add
0.00
P3.13.10.2
P3.13.1.4
0.5
1669
VACON · 172
PARAMETERS MENU