Fault
code
Fault ID
Fault name
Possible cause
How to correct the fault
57
1057
Identification
There was a failure in the
identification run.
Make sure that the motor is con-
nected to the drive.
Make sure that there is no load on
the motor shaft.
Make sure that the start command
is not removed before the identifi-
cation run is complete.
1157
During the identification run
drive was not able to reach
required frequency refer-
ence.
Make sure that minimum and max-
imum frequency references are set
correctly. Too low maximum fre-
quency might prevent drive from
reaching required frequency.
1257
During the identification run
drive was not able to reach
required frequency refer-
ence.
Make sure that acceleration time is
set correctly. Too long acceleration
time might prevent drive from
reaching required frequency in 40
seconds.
1357
During the identification run
drive was not able to reach
required frequency refer-
ence.
Make sure that current, torque and
power limits of the drive are set
correctly. Too low limit settings
might prevent drive from reaching
required frequency.
63
1063
Quick Stop fault
The Quick stop function is
activated
Find the cause for the quick stop
activation. After you find it, correct
it. Reset the fault and restart the
drive.
See parameter P3.5.1.26 and the
quick stop parameters.
1363
Quick Stop alarm
65
1065
PC communication
fault
The data connection
between the PC and the
drive is defective
Do a check of the installation,
cable and terminals between the
PC and the drive.
66
1366
Thermistor input 1
fault
The motor temperature
increased.
Do a check of the motor cooling
and the load.
Do a check of the thermistor con-
nection.
If the thermistor input is not used,
you have to short-circuit it.
Ask instructions from your nearest
distributor.
1466
Thermistor input 2
fault
1566
Thermistor input 3
fault
VACON · 376
FAULT TRACING
11
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/