5.13
GROUP 3.13: PID CONTROLLER
Table 74: PID controller 1 basic settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.13.1.1
PID Gain
0.00
1000.00
%
100.00
118
P3.13.1.2
PID Integration Time
0.00
600.00
s
1.00
119
P3.13.1.3
PID Derivation Time
0.00
100.00
s
0.00
132
P3.13.1.4
Process Unit Selec-
tion
1
46
1
1036
1 = %
2 = 1/min
3 = rpm
4 = ppm
5 = pps
6 = l/s
7 = l/min
8 = l/h
9 = kg/s
10 = kg/min
11 = kg/h
12 = m
3
/s
13 = m
3
/min
14 = m
3
/h
15 = m/s
16 = mbar
17= bar
18 = Pa
19 = kPa
20 = mVS
21 = kW
22 = °C
23 = gal/s
24 = gal/min
25 = gal/h
26 = lb/s
27 = lb/min
28 = lb/h
29 = ft
3
/s
30 = ft
3
/min
31 = ft
3
/h
32 = ft/s
33 = in wg
34 = ft wg
35 = SPI
36 = lb/in
2
37 = psig
38 = hp
39 = °F
40 = ft
41 = inch
42 = mm
43 = cm
44 = m
45 = gpm
46 = cfm
VACON · 162
PARAMETERS MENU
5
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
Содержание 100 flow
Страница 1: ...vacon 100 flow ac drives application manual ...
Страница 2: ......