Table 9: M1 Quick Setup
Index
Parameter
Min
Max
Unit
Default
ID
Description
1.22
I/O Control Refer-
ence A Selection
1
20
6
117
The selection of the
frequency reference
source when the con-
trol place is I/O A.
0 = PC
1 = Preset Frequency 0
2= Keypad Reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID Reference
8 = Motor Potentiome-
ter
11 = Block Out.1
12 = Block Out.2
13 = Block Out.3
14 = Block Out.4
15 = Block Out.5
16 = Block Out.6
17 = Block Out.7
18 = Block Out.8
19 = Block Out.9
20 = Block Out.10
The application that
you set with parameter
1.2 gives the default
value.
1.23
Keypad Control Ref-
erence Selection
1
20
1
121
See P1.22.
1.24
Fieldbus Control
Reference Selection
1
20
2
122
See P1.22.
1.25
AI1 Signal Range
0
1
0
379
0= 0..10V / 0..20mA
1= 2..10V / 4..20mA
1.26
AI2 Signal Range
0
1
1
390
0= 0..10V / 0..20mA
1= 2..10V / 4..20mA
1.27
RO1 Function
0
74
2
11001 See P3.5.3.2.1
1.28
RO2 Function
0
74
3
11004 See P3.5.3.2.1
1.29
RO3 Function
0
74
1
11007 See P3.5.3.2.1
1.30
AO1 Function
0
31
2
10050 See P3.5.4.1.1
QUICK STARTUP GUIDE
VACON · 39
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/