Table 12: M1 Quick setup
Index
Parameter
Min
Max
Unit
Default
ID
Description
1.10
Motor Nom-
inal Fre-
quency
8.0
320.0
Hz
50.0 /
60.0
111
Find this value f
n
on
the nameplate of the
motor.
1.11
Motor Nom-
inal Speed
24
19200
Rpm
Varies
112
Find this value n
n
on
the nameplate of the
motor.
1.12
Motor Nom-
inal Current
I
H
* 0.1
I
S
A
Varies
113
Find this value I
n
on
the nameplate of the
motor.
1.13
Motor Cos
Phi (Power
Factor)
0.30
1.00
Varies
120
Find this value on the
nameplate of the
motor.
1.14
Energy Opti-
misation
0
1
0
666
The drive finds the
minimum motor cur-
rent to use less
energy and to lower
the motor noise. Use
this function with, for
example, fan and
pump processes.
0 = Disabled
1 = Enabled
1.15
Identifica-
tion
0
2
0
631
The identification run
calculates or meas-
ures the motor
parameters that are
necessary for a good
control of the motor
and speed.
0 = No action
1 = At standstill
2 = With rotation
Before you do the
identification run,
you must set the
motor nameplate
parameters.
1.16
Start Func-
tion
0
1
0
505
0 = Ramping
1 = Flying Start
1.17
Stop Func-
tion
0
1
0
506
0 = Coasting
1 = Ramping
QUICK STARTUP GUIDE