Table 116: Fieldbus Control Word
Bit
Descriptions
Value = 0 (FALSE)
Value = 1 (TRUE)
Bit 0
Stop request from Fieldbus
Start request from Fieldbus
Bit 1
Forward direction request
Reverse direction request
Bit 2
No action
Reset active faults and alarms (on rising
edge 0=>1)
Bit 3
No action
Force stop mode to Coasting
Bit 4
No action
Force stop mode to Ramping
Bit 5
No action
(normal deceleration ramp time)
Force drive to use fast deceleration ramp
time
(1/3 of normal deceleration time)
Bit 6
No action
Freeze drive frequency reference
Bit 7
No action
Force Fieldbus frequency reference to zero
Bit 8
No action
Force drive control place to Fieldbus con-
trol
Bit 9
No action
Force drive reference source to Fieldbus
reference
Bit 10
Reserved
Reserved
Bit 11
Reserved
Reserved
Bit 12
No action
Activate Quick Stop function
NOTE!
This will stop the drive according to set-
ting in parameter menu M3.8.5.
Bit 13
Reserved
Reserved
Bit 14
Reserved
Reserved
Bit 15
Reserved
Reserved
V2.12.2 FB SPEED REFERENCE (ID 875)
This monitoring value shows the fieldbus frequency reference as a percentage of minimum
frequency to maximum frequency.
The speed reference information is scaled between the minimum and the maximum
frequency at the moment when the application received it. You can change the minimum and
the maximum frequencies after the application received the reference without an effect on
the reference.
VACON · 212
MONITORING VALUE DESCRIPTIONS
9