Table 9: M1 Quick Setup
Index
Parameter
Min
Max
Unit
Default
ID
Description
1.2
Application
0
4
2
212
0 = Standard
1 = HVAC
2 = PID Control
3 = Multi-pump (single
drive)
4 = Multi-pump (multi-
drive)
1.3
Minimum Frequency
Reference
0.00
P1.4
Hz
0.0
101
The minimum fre-
quency reference that
is accepted.
1.4
Maximum Frequency
Reference
P1.3
320.0
Hz
50.0 /
60.0
102
The maximum fre-
quency reference that
is accepted.
1.5
Acceleration Time 1
0.1
3000.0
s
5.0
103
Gives the quantity of
time that is necessary
for the output fre-
quency to increase
from 0 frequency to the
maximum frequency.
1.6
Deceleration Time 1
0.1
3000.0
s
5.0
104
Gives the quantity of
time that is necessary
for the output fre-
quency to decrease
from the maximum
frequency to 0 fre-
quency.
1.7
Motor Current Limit
I
H
*0.1
I
S
A
Varies
107
The maximum motor
current from the AC
drive.
1.8
Motor Type
0
2
0
650
0 = Induction Motor
1 = Permanent Magnet
Motor
2 = Reluctance Motor
1.9
Motor Nominal Volt-
age
Varies
Varies
V
Varies
110
Find this value U
n
on
the nameplate of the
motor.
NOTE!
Find out if the motor
connection is Delta or
Star.
VACON · 36
QUICK STARTUP GUIDE
1
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/