Table 3: M1 Quick Setup
Index
Parameter
Min
Max
Unit
Default
ID
Description
1.10
Motor Nominal Fre-
quency
8.0
320.0
Hz
50 / 60
111
Find this value f
n
on
the nameplate of the
motor.
1.11
Motor Nominal
Speed
24
19200
Rpm
Varies
112
Find this value n
n
on
the nameplate of the
motor.
1.12
Motor Nominal Cur-
rent
I
H
* 0.1
I
H
* 2
A
Varies
113
Find this value I
n
on
the nameplate of the
motor.
1.13
Motor Cos Phi
(Power Factor)
0.30
1.00
Varies
120
Find this value on the
nameplate of the
motor.
1.14
Energy Optimisation
0
1
0
666
The drive finds the
minimum motor cur-
rent to use less energy
and to lower the motor
noise. Use this function
with, for example, fan
and pump processes.
0 = Disabled
1 = Enabled
1.15
Identification
0
2
0
631
The identification run
calculates or measures
the motor parameters
that are necessary for
a good control of the
motor and speed.
0 = No action
1 = At standstill
2 = With rotation
Before you do the iden-
tification run, you must
set the motor name-
plate parameters.
1.16
Start Function
0
1
0
505
0 = Ramping
1 = Flying Start
1.17
Stop Function
0
1
0
506
0 = Coasting
1 = Ramping
QUICK STARTUP GUIDE
VACON · 19
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
1