Table 121: The output signals through RO1
Selection
number
Selection name
Description
23
Input pressure alarm
The input pressure of the pump is below the value that was
set with parameter P3.13.9.7.
24
Frost protection alarm
The measured temperature of the pump is below the level
that was set with parameter P3.13.10.5.
25
Time channel 1
The status of Time channel 1.
26
Time channel 2
The status of Time channel 2.
27
Time channel 3
The status of Time channel 3.
28
Fieldbus Control Word bit 13
The digital (relay) output control from the Fieldbus control
word bit 13.
29
Fieldbus Control Word bit 14
The digital (relay) output control from the Fieldbus control
word bit 14.
30
Fieldbus Control Word bit 15
The digital (relay) output control from the Fieldbus control
word bit 15.
31
Fieldbus Process Data In1 bit 0
The digital (relay) output control from the Fieldbus process
data In1, bit 0.
32
Fieldbus Process Data In1 bit 1
The digital (relay) output control from the Fieldbus process
data In1, bit 1.
33
Fieldbus Process Data In1 bit 2
The digital (relay) output control from the Fieldbus process
data In1, bit 2.
34
Maintenance counter 1 alarm
The maintenance counter goes to the alarm limit that is set
with parameter P3.16.2.
35
Maintenance counter 1 fault
The maintenance counter goes to the alarm limit that is set
with parameter P3.16.3.
36
Block Out.1
The output of the programmable Block 1. See parameter
menu M3.19 Block Programming.
37
Block Out.2
The output of the programmable Block 2. See parameter
menu M3.19 Block Programming.
38
Block Out.3
The output of the programmable Block 3. See parameter
menu M3.19 Block Programming.
39
Block Out.4
The output of the programmable Block 4. See parameter
menu M3.19 Block Programming.
40
Block Out.5
The output of the programmable Block 5. See parameter
menu M3.19 Block Programming.
41
Block Out.6
The output of the programmable Block 6. See parameter
menu M3.19 Block Programming.
VACON · 274
PARAMETER DESCRIPTIONS
10
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
Содержание 100 flow
Страница 1: ...vacon 100 flow ac drives application manual ...
Страница 2: ......
Страница 6: ...VACON 6 LOCAL CONTACTS HTTP DRIVES DANFOSS COM DANFOSS DRIVES LOCAL CONTACTS ...