Necessary step
Activated frequency
Make a selection of the value 0 for parameter P3.3.1.5. Preset frequency 0
Table 118: The selection of preset frequencies when P3.3.3.1 = Binary coded
Activated digital input signal
Activated frequency
reference
Preset Freq Sel2
(P3.3.3.12)
Preset Freq Sel1
(P3.3.3.11)
Preset Freq Sel0
(P3.3.3.10)
Preset frequency 0
Only if Preset Freq 0 is set
as frequency reference
source with P3.3.3.1.5,
P3.3.1.6, P3.3.1.7 or
P3.3.1.10.
*
Preset frequency 1
*
Preset frequency 2
*
*
Preset frequency 3
*
Preset frequency 4
*
*
Preset frequency 5
*
*
Preset frequency 6
*
*
*
Preset frequency 7
* = the input is activated.
VALUE 1 SELECTED FOR PARAMETER P3.3.3.1:
You can use the Preset Frequencies 1 to 3 with different sets of active digital inputs. The
number of active inputs tells which one is used.
PARAMETER DESCRIPTIONS
VACON · 243
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/