Table 10: M1.34 Multi-pump (single drive)
Index
Parameter
Min
Max
Unit
Default
ID
Description
1.34.16
Autochange
0
2
1
1027
Disable/enable the
rotation of the start
order and the pri-
ority of the motors.
0 = Disabled
1 = Enabled (inter-
val)
2 = Enabled (week-
days)
1.34.17
Autochanged
Pump
0
1
1
1028
0 = Auxiliary Pump
1 = All Pumps
1.34.18
Autochange
Interval
0.0
3000.0
h
48.0
1029
When the time
specified by the
this parameter is
used, the autoch-
ange function
starts. But the
autochange starts
only if the capacity
is below the level
specified by
parameters
P1.34.21 and
P1.34.22.
1.34.19
Autochange Days
0
127
15904
Range
B0 = Sunday
B1 = Monday
B2 = Tuesday
B3 = Wednesday
B4 = Thursday
B5 = Friday
B6 = Saturday
1.34.20
Autochange Time
of Day
00:00:00
23:59:59
Time
15905
Range:
00:00:00-23:59:59
1.34.21
Autochange:
Frequency Limit
0.00
P3.3.1.2
Hz
25:00
1031
These parameters
set the level below
which the capacity
must stay for the
autochange to
start.
1.34.22
Autochange:
Pump Limit
1
6
1030
VACON · 42
QUICK STARTUP GUIDE
1
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/