17
Set the signal range of the analogue input
0 = 0-10V / 0-20mA
1 = 2-10V / 4-20mA
18
Set a value for P3.13.1.8 Error Inversion
0 = Normal
1 = Inverted
19
Set a value for P3.13.2.6 Setpoint Source Selection
See table Setpoints in Table 75 Setpoint set-
If you select an analogue input signal, step 20 shows first, and then step 22 shows. With
other selections, the wizard goes to step 21.
If you set Keypad Setpoint 1 or Keypad Setpoint 2 as the value, the wizard goes directly to step
22.
20
Set the signal range of the analogue input
0 = 0-10V / 0-20mA
1 = 2-10V / 4-20mA
21
Set a value for P3.13.2.1 (Keypad Setpoint 1) and
P3.13.2.2 (Keypad Setpoint 2)
Specified by the range set in step 19
22
Use the sleep function
0 = No
1 = Yes
If you give the value Yes in step 22, you see the next 3 steps. If you give the value No, the
wizard goes to step 26.
23
Set a value for P3.13.5.1 SP1 Sleep Frequency Limit Range: 0.00-320.00 Hz
24
Set a value for P3.13.5.2 SP1 Sleep Delay
Range: 0-3000 s
25
Set a value for P3.13.5.3 SP1 Wake Up Level
The range is specified by the set process
unit.
26
Set a value for P3.15.2 Number of pumps
Range: 1-8
27
Set a value for P3.15.5 Pump Interlocking
0 = Not used
1 = Enabled
28
Set a value for P3.15.6 Autochange
0 = Disabled
1 = Enabled (Interval)
2 = Enabled (Weekdays)
If you set the value Enabled (Interval or Weekdays) to parameter Autochange, steps 29-34
show. If you set the value Disabled to parameter Autochange, the wizard goes directly to step
35.
WIZARDS
VACON · 83
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
2