Fault
code
Fault ID
Fault name
Possible cause
How to correct the fault
47
663
Software updated
The software of the drive
was updated, the full soft-
ware package or an applica-
tion.
No steps are necessary.
50
1050
AI low fault
1 or more of the available
analogue input signals is
below 50% of the minimum
signal range.
A control cable is defective
or loose.
A malfunction in a signal
source.
Replace the defective parts.
Do a check of the analogue input
circuit.
Make sure that parameter AI1 Sig-
nal Range is set correctly.
51
1051
Device external fault
The digital input signal that
is set with parameter
P3.5.1.11 or P3.5.1.12 was
activated.
This is a user-specified fault.
Do a check of the digital inputs and
schematics.
52
1052
Keypad communica-
tion fault
The connection between the
control panel and the drive
is defective.
Do a check of the control panel
connection and the control panel
cable if you have it.
1352
53
1053
Fieldbus communica-
tion fault
The data connection
between the fieldbus master
and the fieldbus board is
defective.
Do a check of the installation and
fieldbus master.
54
1354
Slot A fault
A defective option board or
slot
Do a check of the board and the
slot.
Ask instructions from your nearest
distributor.
1454
Slot B fault
1554
Slot C fault
1654
Slot D fault
1754
Slot E fault
FAULT TRACING