5.15
GROUP 3.15: MULTI-PUMP
Table 89: Multi-pump parameters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.15.1
Multi-pump Mode
0
2
0 *
1785
0 = Single Drive
1 = Multifollower
2 = Multimaster
P3.15.2
Number of Pumps
1
8
1 *
1001
P3.15.3
Pump ID Number
1
8
0
1500
P3.15.4
Start and Feedback
Signals
0
2
1
1782
0 = Not Connected
1 = Only Start Signal
Connected
2 = Both Signals Con-
nected
P3.15.5
Pump Interlocking
0
1
1 *
1032
0 = Not used
1 = Enabled
P3.15.6
Autochange
0
2
1 *
1027
0 = Disabled
1 = Enabled (interval)
2 = Enabled (weekdays)
P3.15.7
Autochanged Pumps
0
1
1 *
1028
0 = Auxiliary pumps
1 = All pumps
P3.15.8
Autochange Interval
0.0
3000.0
h
48.0 *
1029
P3.15.9
Autochange Days
0
127
0
1786
B0 = Sunday
B1 = Monday
B2 = Tuesday
B3 = Wednesday
B4 = Thursday
B5 = Friday
B6 = Saturday
P3.15.10
Autochange: Time of
Day
00:00:00 23:59:59
Time
00:00:00
1787
P3.15.11
Autochange: Fre-
quency Limit
0.00
P3.3.1.2
Hz
25.00 *
1031
P3.15.12
Autochange: Pump
Limit
0
8
1 *
1030
P3.15.13
Bandwidth
0
100
%
10 *
1097
Setpoint = 5 bar
Bandwidth = 10%.
P3.15.14
Bandwidth Delay
0
3600
s
10 *
1098
P3.15.15
Constant Production
Speed
0.0
100.0
%
80.0 *
1513
PARAMETERS MENU
VACON · 177
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
5
Содержание 100 flow
Страница 1: ...vacon 100 flow ac drives application manual ...
Страница 2: ......
Страница 6: ...VACON 6 LOCAL CONTACTS HTTP DRIVES DANFOSS COM DANFOSS DRIVES LOCAL CONTACTS ...