Fault
code
Fault ID
Fault name
Possible cause
How to correct the fault
68
1301
Maintenance counter
1 alarm
The value of the mainte-
nance counter is higher than
the alarm limit.
Do the necessary maintenance.
Reset the counter. See parameter
B3.16.4 or P3.5.1.40.
1302
Maintenance counter
1 fault
The value of the mainte-
nance counter is higher than
the fault limit.
1303
Maintenance counter
2 alarm
The value of the mainte-
nance counter is higher than
the alarm limit.
1304
Maintenance counter
2 fault
The value of the mainte-
nance counter is higher than
the fault limit.
69
1310
Fieldbus communica-
tion fault
The ID number that is used
to map the values to Field-
bus Process Data Out is not
valid.
Do a check of the parameters in
the Fieldbus Data Mapping menu.
1311
It is not possible to convert 1
or more values for Fieldbus
Process Data Out.
The type of the value is not speci-
fied. Do a check of the parameters
in the Fieldbus Data Mapping
menu.
1312
There is an overflow when
the values for Fieldbus
Process Data Out (16-bit)
are mapped and converted.
Do a check of the parameters in
the Fieldbus Data Mapping menu.
76
1076
Start prevented
The start command is
blocked to prevent the acci-
dental rotation of the motor
during the first power-up.
Reset the drive to start the correct
operation. The parameter settings
tell if it is necessary to restart the
drive.
77
1077
>5 connections
There are more than 5
active fieldbus or PC tool
connections. You can use
only 5 connections at the
same time.
Keep 5 active connections. Remove
the other connections.
100
1100
Soft fill timeout
There is a timeout in the
Soft fill function in the PID
controller. The drive did not
go to the process value in
the time limit.
A pipe that broke can be the
cause.
Do a check of the process.
Do a check of the parameters in
the menu M3.13.8.
FAULT TRACING