V2.3.11 UNIT TEMPERATURE (ID 8)
This monitoring value shows the measured heatsink temperature of the drive.
The unit of the monitoring value is celsius degrees or fahrenheit degrees, depending on the
'C/F Selection' parameter value.
V2.3.12 MOTOR TEMPERATURE (ID 9)
This monitoring value shows the calculated motor temperature in percentage of the nominal
working temperature.
When the value rises above 105%, motor thermal protection fault occurs.
V2.3.13 MOTOR PREHEAT (ID 1228)
This monitoring value shows the status of the motor preheat function.
V2.3.15 KWH TRIP COUNTER LOW (ID 1054)
This monitoring value shows the actual value of the kWh counter (energy counter).
When the value of the counter goes higher than 65535, the counter is restarted from 0.
V2.3.16 KWH TRIP COUNTER HIGH (ID 1067)
This monitoring value shows how many times the kWh counter (energy counter) has spinned
around.
9.2
I/O
V2.4.1 SLOTA DIN 1,2,3 (ID 15)
This monitoring value shows the status of the digital inputs 1-3 in slot A (standard I/O).
V2.4.2 SLOTA DIN 4,5,6 (ID 16)
This monitoring value shows the status of the digital inputs 4-6 in slot A (standard I/O).
V2.4.3 SLOTB RO 1,2,3 (ID 17)
This monitoring value shows the status of the relay outputs 1-3 in slot B.
V2.4.4 ANALOG INPUT 1 (ID 59)
This monitoring value shows the value of the analogue input signal as a percentage of the
used range.
V2.4.5 ANALOG INPUT 2 (ID 60)
This monitoring value shows the value of the analogue input signal as a percentage of the
used range.
VACON · 204
MONITORING VALUE DESCRIPTIONS
9