Table 12: M1 Quick setup
Index
Parameter
Min
Max
Unit
Default
ID
Description
1.2
Application
0
4
2
212
0 = Standard
1 = HVAC
2 = PID Control
3 = Multi-pump (sin-
gle drive)
4 = Multi-pump
(multidrive)
1.3
Minimum
Frequency
Reference
0.00
P1.4
Hz
0.0
101
The minimum fre-
quency reference
that is accepted.
1.4
Maximum
Frequency
Reference
P1.3
320.0
Hz
50.0 /
60.0
102
The maximum fre-
quency reference
that is accepted.
1.5
Acceleration
Time 1
0.1
3000.0
s
5.0
103
Gives the quantity of
time that is neces-
sary for the output
frequency to
increase from 0 fre-
quency to the maxi-
mum frequency.
1.6
Deceleration
Time 1
0.1
3000.0
s
5.0
104
Gives the quantity of
time that is neces-
sary for the output
frequency to
decrease from the
maximum frequency
to 0 frequency.
1.7
Motor Cur-
rent Limit
I
H
*0.1
I
S
A
Varies
107
The maximum motor
current from the AC
drive.
1.8
Motor Type
0
2
0
650
0 = Induction Motor
1 = Permanent Mag-
net Motor
2 = Reluctance
Motor
1.9
Motor Nom-
inal Voltage
Varies
Varies
V
Varies
110
Find this value U
n
on
the nameplate of the
motor.
NOTE!
Find out if the
motor connection is
Delta or Star.
VACON · 68
QUICK STARTUP GUIDE
1
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/