Table 95: Fire mode parameters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.17.9
Fire Mode Run Indi-
cation Current
0
100
%
10
15580
5.18
GROUP 3.18: MOTOR PREHEAT PARAMETERS
Table 96: Motor preheat parameters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.18.1
Motor Preheat Func-
tion
0
3
0
1225
0 = Not used
1 = Always in stop state
2 = Controlled by DI
3 = Temperature limit,
heatsink
P3.18.2
Preheat Tempera-
ture Limit
-20
100
°C/F
0
1226
P3.18.3
Motor Preheat Cur-
rent
0
0.5*I
L
A
Varies
1227
P3.18.4
Motor Preheat ON
Varies
Varies
DigIN
Slot0.1
1044
OPEN = No action
CLOSED = Preheat
activated in Stop state
5.19
GROUP 3.19: DRIVE CUSTOMIZER
Table 97: Drive customizer parameters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.19.1
Operation Mode
0
1
1
15001 0 = Execute Program
1 = Programming
NOTE!
When you use the Drive customizer, use the graphical Drive customizer tool in
VACON
®
Live.
VACON · 182
PARAMETERS MENU
5
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/