Table 7: M1.33 PID control
Index
Parameter
Min
Max
Unit
Default
ID
Description
1.33.1
PID Gain
0.00
100.00
%
100.00
118
If the value of the
parameter is set to
100%, a change of 10%
in the error value cau-
ses the controller out-
put to change by 10%.
1.33.2
PID Integration Time
0.00
600.00
s
1.00
119
If this parameter is set
to, 1,00 s, a change of
10% in the error value
causes the controller
output to change by
10.00%/s.
1.33.3
PID Derivation Time
0.00
100.00
s
0.00
1132
If this parameter is set
to 1,00 s, a change of
10% in the error value
during 1.00 s causes
the controller output to
change by 10.00%.
1.33.4
Process Unit Selec-
tion
1
44
1
1036
Select the unit of the
process. See P3.13.1.4
1.33.5
Process Unit Min
Varies
Varies
Varies
1033
The process unit value
that is the same as 0%
of the PID feedback
signal.
1.33.6
Process Unit Max
Varies
Varies
Varies
1034
The process unit value
that is the same as
100% of the PID feed-
back signal.
1.33.7
Feedback 1 Source
Selection
0
30
2
334
See P3.13.3.3
1.33.8
Setpoint 1 Source
Selection
0
32
1
332
See P3.13.2.6
1.33.9
Keypad Setpoint 1
Varies
Varies
Varies
0
167
1.33.10
SP1 Sleep Frequency
Limit
0.0
320.0
Hz
0.0
1016
The drive goes to the
sleep mode when the
output frequency stays
below this limit for lon-
ger than is specified by
parameter Sleep Delay.
0 = Not used