Operation
6.11 Communication via EtherNet/IP
Enclosed Drives
414
Operating Instructions, 12/2018, A5E36652151A
6.11.5
Integrate the drive device into the Ethernet network via DHCP
Integrating the drive into the EtherNet/IP network via the onboard PROFINET interface X150.
Proceed as follows to integrate the drive into EtherNet/IP:
1.
Set p8924 (PN DHCP mode) = 2 or 3
Parameterization Meaning
p8924 = 2
The DHCP server assigns the IP address based on the MAC address.
p8924 = 3
The DHCP server assigns the IP address based on the station name.
2.
Save the settings with p8925 = 2.
The next time that it is run-up, the drive retrieves the IP address made available by a
DHCP server. After the drive has run-up, you can address the drive as Ethernet
participant.
Note
Immediate switchover without restart
The switchover to DHCP is performed immediately and without a restart if the change is
carried out with the EIP command "Set Attribute Single" (class F5 hex, attribute 3), e.g.
using:
•
An EIP control
•
An EIP commissioning tool
Displays:
●
r8930: Station name of the onboard PROFINET interface X150
●
r8934: DHCP mode of the onboard PROFINET interface X150
●
r8935: MAC address of the onboard PROFINET interface X150
Содержание SINAMICS S150 NEMA
Страница 1: ......
Страница 2: ......
Страница 20: ...Table of contents Enclosed Drives 18 Operating Instructions 12 2018 A5E36652151A ...
Страница 42: ...Device overview 2 5 Rating plate Enclosed Drives 40 Operating Instructions 12 2018 A5E36652151A ...
Страница 200: ...Electrical installation 4 9 Additional connections Enclosed Drives 198 Operating Instructions 12 2018 A5E36652151A ...
Страница 500: ...Output terminals 8 3 Digital outputs Enclosed Drives 498 Operating Instructions 12 2018 A5E36652151A ...
Страница 828: ...Technical specifications 12 3 Technical specifications Enclosed Drives 826 Operating Instructions 12 2018 A5E36652151A ...
Страница 861: ......
Страница 862: ......