Commissioning
5.3 Procedure for commissioning with STARTER
Enclosed Drives
244
Operating Instructions, 12/2018, A5E36652151A
6.
The SINAMICS drive object is detected and displayed as a bus node with IP address
169.254.11.22 and without name.
Figure 5-39 Accessible nodes
7.
Mark the bus node entry and select the displayed menu item "Edit Ethernet node" with
the right mouse button.
8.
In the following "Edit Ethernet node" screen, enter the device name for the Ethernet
interface ("drive1", for example) and click the "Assign name" button. Enter the IP address
(e.g. 169.254.11.10) in the IP configuration and specify the subnet screen (e.g.
255.255.255.0). Then click the "Assign IP configuration" button and close the mask.
Содержание SINAMICS S150 NEMA