![Siemens SINAMICS S150 NEMA Скачать руководство пользователя страница 77](http://html.mh-extra.com/html/siemens/sinamics-s150-nema/sinamics-s150-nema_operating-instructions-manual_381570077.webp)
Electrical installation
4.6 Power connections
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
75
Figure 4-6
Setting terminals for the fan transformers (380 to 480 V 3 AC / 500 to 690 V 3 AC)
The line voltage assignments for making the appropriate setting on the fan transformer are
indicated in the following tables.
Note
Fan transformer for 660 to 690 V 3 AC
With the 500 V to 690 V 3 AC fan transformer, a jumper is inserted between the "600 V"
terminal and "CON" terminal. The jumper between terminal "600 V" and "CON" is for internal
use.
WARNING
Fire due to overheating resulting from insufficient equipment fan voltage
If the terminals are not reconnected to correspond with the actual line voltage, overheating
and risks to personnel due to smoke and fire may result.
This can also cause the fan fuses to rupture due to overload.
•
Set the terminals in accordance with the actual line voltage.
Note
Article numbers for fan fuses
The article numbers for fan fuses that have blown can be found in the spare parts list.
Table 4- 5
Line voltage assignment for the setting at the fan transformer (3-phase 380 ... 480 V AC)
Line voltage
Taps of the fan transformer (-G1-T10, -T1-T10)
380 V ± 10%
380 V
400 V ± 10%
400 V
440 V ± 10%
440 V
480 V ± 10%
480 V
Содержание SINAMICS S150 NEMA
Страница 1: ......
Страница 2: ......
Страница 20: ...Table of contents Enclosed Drives 18 Operating Instructions 12 2018 A5E36652151A ...
Страница 42: ...Device overview 2 5 Rating plate Enclosed Drives 40 Operating Instructions 12 2018 A5E36652151A ...
Страница 200: ...Electrical installation 4 9 Additional connections Enclosed Drives 198 Operating Instructions 12 2018 A5E36652151A ...
Страница 500: ...Output terminals 8 3 Digital outputs Enclosed Drives 498 Operating Instructions 12 2018 A5E36652151A ...
Страница 828: ...Technical specifications 12 3 Technical specifications Enclosed Drives 826 Operating Instructions 12 2018 A5E36652151A ...
Страница 861: ......
Страница 862: ......