Operation
6.7 Communication according to PROFIdrive
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
345
The other diagnostics data (types) can be in any sequence. This is the reason that the
following diagnostics data include a header:
●
Identifier-related diagnostics
●
Status messages/module status
●
Channel-related diagnostics
The diagnostic data type can be uniquely identified based on the header.
Note
The master must operate in the DPV1 mode.
Standard diagnostics
For communication via PROFIBUS, standard diagnostics is structured as follows.
Bit
7
6
5
4
3
2
1
0
Octet
Name
1
Station
status 1
Master_
Lock
= 0
Prm_Fault
0
Not_
Supported
Ext_Diag Cfg_Fault Station_
Not_
Ready
Station_
Non_
Exist
= 0
2
Station
status 2
0
0
Sync_
Mode
Freeze_
Mode
WD_On
1
Stat_Diag
= 0
Prm_Req
3
Station
status 3
Ext_
Diag_
Overflow
0
0
0
0
0
0
0
4
Master_Add
5
Ident_Number (HighByte) of the slave
6
Ident_Number (LowByte) of the slave
In this context, the following values are decisive for diagnostics:
●
Ext_Diag
–
Group signal for diagnostics in the slave
–
= 1, if at least 1 alarm is active
●
Ext_Diag_Overflow
Display, diagnostics overflow in the slave (for more than 240 bytes)
Содержание SINAMICS S150 NEMA
Страница 1: ......
Страница 2: ......
Страница 20: ...Table of contents Enclosed Drives 18 Operating Instructions 12 2018 A5E36652151A ...
Страница 42: ...Device overview 2 5 Rating plate Enclosed Drives 40 Operating Instructions 12 2018 A5E36652151A ...
Страница 200: ...Electrical installation 4 9 Additional connections Enclosed Drives 198 Operating Instructions 12 2018 A5E36652151A ...
Страница 500: ...Output terminals 8 3 Digital outputs Enclosed Drives 498 Operating Instructions 12 2018 A5E36652151A ...
Страница 828: ...Technical specifications 12 3 Technical specifications Enclosed Drives 826 Operating Instructions 12 2018 A5E36652151A ...
Страница 861: ......
Страница 862: ......