Output terminals
8.3 Digital outputs
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
497
Selection of possible connections for the digital outputs
Table 8- 6
Selection of possible connections for the digital outputs
Signal
Bit in status
word 1
Parameter
1 = Ready to start
0
r0899.0
1 = Ready
1
r0899.1
1 = Operation enabled
2
r0899.2
1 = Fault present
3
r2139.3
0 = Coast to stop active (OFF2 active)
4
r0899.4
0 = Fast stop active (OFF3 active)
5
r0899.5
1 = Closing lockout active
6
r0899.6
1 = Alarm present
7
r2139.7
1 = Speed setpoint/actual deviation within the tolerance band
8
r2197.7
1 = Master control requested
9
r0899.9
1 = f or n comparison value reached or exceeded
10
r2199.1
1 = I, M or P limit reached
11
r1407.7
1 = Open holding brake
12
r0899.12
0 = Alarm, motor overtemperature
13
r2135.14
1 = Motor rotates forward (n_act
≥
0)
0 = Motor rotates backward (n_act < 0)
14
r2197.3
0 = Alarm thermal overload in power unit (A5000)
15
r2135.15
1 = Pulses enabled
r0899.11
1 = n_act
≤
p2155
r2197.1
1 = n_act > p2155
r2197.2
1 = Ramp-up/ramp-down completed
r2199.5
1 = |n_act| < p2161 (preferably as n_min or n=0 message)
r2199.0
1 = |M_set| < p2174
r2198.10
1 = LOCAL mode active (control via operator panel or control panel)
r0807.0
1 = Motor blocked
r2198.6
Содержание SINAMICS S150 NEMA
Страница 1: ......
Страница 2: ......
Страница 20: ...Table of contents Enclosed Drives 18 Operating Instructions 12 2018 A5E36652151A ...
Страница 42: ...Device overview 2 5 Rating plate Enclosed Drives 40 Operating Instructions 12 2018 A5E36652151A ...
Страница 200: ...Electrical installation 4 9 Additional connections Enclosed Drives 198 Operating Instructions 12 2018 A5E36652151A ...
Страница 500: ...Output terminals 8 3 Digital outputs Enclosed Drives 498 Operating Instructions 12 2018 A5E36652151A ...
Страница 828: ...Technical specifications 12 3 Technical specifications Enclosed Drives 826 Operating Instructions 12 2018 A5E36652151A ...
Страница 861: ......
Страница 862: ......