Commissioning
5.3 Procedure for commissioning with STARTER
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
243
7.
Set the IP address of the PG/PC access interface to the Control Unit to 169.254.11.1 and
the subnet mask to 255.255.0.0.
Figure 5-38 Internet Protocol (TCP/IP) properties
8.
Click "OK" and close the Windows-specific window of the network connections.
Assigning the IP address and the name via STARTER, "Accessible nodes" function
Use the STARTER to assign an IP address and a name to the Ethernet interface.
1.
Connect the PG/PC and the Control Unit using an Ethernet cable.
2.
Switch on the Control Unit.
3.
Open STARTER.
4.
Create a new project or open an existing project.
5.
Search for available nodes in Ethernet via Project -> Accessible nodes or the "Accessible
nodes" button.