Functions, monitoring and protective functions
9.3 Drive functions
Enclosed Drives
568
Operating Instructions, 12/2018, A5E36652151A
Activating know-how protection
Know-how protection is activated via STARTER in the online mode as follows:
●
Select the drive unit via Project > Know-how protection drive unit > Activate.
●
A dialog appears in which the following settings can be made:
–
It can be selected as to whether know-how protection should be realized with or
without copy protection:
- Without copy protection (factory setting)
- With basic copy protection (permanently linked to the memory card)
- With extended copy protection (permanently linked to the memory card and Control
Unit)
Further, you can select whether diagnostic functions are permitted.
–
By clicking on Define an additional dialog opens, in which the password can be
entered and acknowledged. The password must comprise at least one character,
it may not exceed a length of 30 characters, all characters are permissible.
Note
Password check for know-how protection and Windows language settings
A change to the Windows language settings after activating know-how protection can
cause errors for a subsequent password verification. As a consequence, only
characters from the ASCII character set should be used for the password.
–
If Copy from RAM to ROM is selected, the settings are permanently saved after exiting
the screen form.
If Copy RAM to ROM is not selected, then the settings for know-how protection are
only saved non-retentively and are no longer available after the system has been
switched on the next time.
●
After the dialog is closed with OK, know-how protection is activated and the data
(parameters, DCC) are saved as encrypted data on the memory card. If larger data
volumes must be encrypted, then a progress display informs you that the encryption or
the activation of the know-how protection is still running.
In all protected adjustable parameters in the expert list, instead of the parameter value,
the text "know-protected" is shown.
Note
For published DCC parameters, the entry "--" appears in the expert list instead of the text
"Know-how protected".
Содержание SINAMICS S150 NEMA
Страница 1: ......
Страница 2: ......
Страница 20: ...Table of contents Enclosed Drives 18 Operating Instructions 12 2018 A5E36652151A ...
Страница 42: ...Device overview 2 5 Rating plate Enclosed Drives 40 Operating Instructions 12 2018 A5E36652151A ...
Страница 200: ...Electrical installation 4 9 Additional connections Enclosed Drives 198 Operating Instructions 12 2018 A5E36652151A ...
Страница 500: ...Output terminals 8 3 Digital outputs Enclosed Drives 498 Operating Instructions 12 2018 A5E36652151A ...
Страница 828: ...Technical specifications 12 3 Technical specifications Enclosed Drives 826 Operating Instructions 12 2018 A5E36652151A ...
Страница 861: ......
Страница 862: ......