Setpoint channel and closed-loop control
7.4 Vector speed/torque control with/without an encoder
Enclosed Drives
472
Operating Instructions, 12/2018, A5E36652151A
Figure 7-15 Speed controller with pre-control
When correctly adapted, when accelerating, the speed controller only has to compensate
disturbance variables in its control loop. This is achieved with a relatively minor controlled
variable change at the controller output. Speed setpoint changes, on the other hand, are
carried out without involving the speed controller and are, therefore, performed more quickly.
The effect of the pre-control variable can be adapted according to the application using the
weighting factor p1496. For p1496 = 100%, precontrol is calculated according to the motor
and load moment of inertia (p0341, p0342). A balancing filter is used automatically to
prevent the speed controller acting against the injected torque setpoint. The time constant of
the balancing filter corresponds to the equivalent delay time of the speed control loop. Speed
controller pre-control is correctly set (p1496 = 100%, calibration using p0342) if the I
component of the speed controller (r1482) does not change while ramping-up or ramping-
down in the range n > 20% x p0310. Thus, pre-control allows a new speed setpoint to be
approached without overshoot (prerequisite: torque limiting does switch in and the moment
of inertia remains constant).
If the speed controller is pre-controlled by means of injection, the speed setpoint (r0062) is
delayed with the same smoothing time (p1442 or p1452) as the actual value (r1445). This
ensures that no target/actual difference (r0064) occurs at the controller input during
acceleration, which would be attributable solely to the signal propagation time.
When speed pre-control is activated, the speed setpoint must be specified continuously or
without a higher interference level (avoids sudden torque changes). An appropriate signal
can be generated by smoothing the speed setpoint or activating ramp-function generator
rounding p1130 – p1131.
The startup time r0345 (T
startup
) is a measure for the total moment of inertia J of the machine
and describes the time during which the unloaded drive can be accelerated with the rated
motor torque r0333 (M
mot,rated
) from standstill to the rated motor speed p0311 (n
mot,rated
).
r0345 = T
startup
= J x (2 x
π
x n
mot,rated
) / (60 x M
mot,rated
) = p0341 x p0342 x (2 x
π
x p0311) /
(60 x r0333)
Содержание SINAMICS S150 NEMA
Страница 1: ......
Страница 2: ......
Страница 20: ...Table of contents Enclosed Drives 18 Operating Instructions 12 2018 A5E36652151A ...
Страница 42: ...Device overview 2 5 Rating plate Enclosed Drives 40 Operating Instructions 12 2018 A5E36652151A ...
Страница 200: ...Electrical installation 4 9 Additional connections Enclosed Drives 198 Operating Instructions 12 2018 A5E36652151A ...
Страница 500: ...Output terminals 8 3 Digital outputs Enclosed Drives 498 Operating Instructions 12 2018 A5E36652151A ...
Страница 828: ...Technical specifications 12 3 Technical specifications Enclosed Drives 826 Operating Instructions 12 2018 A5E36652151A ...
Страница 861: ......
Страница 862: ......