![Siemens SINAMICS S150 NEMA Скачать руководство пользователя страница 839](http://html.mh-extra.com/html/siemens/sinamics-s150-nema/sinamics-s150-nema_operating-instructions-manual_381570839.webp)
Appendix
A.3 Parameter macros
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
837
A.3
Parameter macros
Parameter macro p0015 = S150 cabinet unit
This macro is used to make default settings for operating the cabinet unit.
Table A- 1
Parameter macro p0015 = S150 cabinet unit
Sink
Source
Parameter
Description
DO Parameter
Description
DO
p0500
Technology application
Vector 0
Standard drive
Vector
p0600
Motor temperature sensor for
monitoring
Vector 0
No sensor
Vector
p0601
Motor temperature sensor type
Vector 0
No sensor
Vector
p0603
CI: Motor temperature
Vector r4105
Sensor on TM31
TM31
p0604
Motor overtemperature alarm
threshold
Vector 120
120 °C
Vector
p0605
Motor overtemperature fault
threshold
Vector 155
155 °C
Vector
p0606
Motor overtemperature timer
Vector 0
0 s
Vector
p0610
Response to motor overtemperature
condition
Vector 12
Messages, no reduction of I_max,
temperature saved
Vector
p0700[0]
Macro binector input (BI)
Vector 70005
PROFIdrive
Vector
p0857
Power unit monitoring time
Vector 30000
30 s
Vector
p0864
BI: Infeed operation
Vector r0863.0
Drive link - open-loop control
A_INF
p1000[0]
Macro connector inputs (CI) for
speed setpoints
Vector 100001
PROFIdrive
Vector
p1001
CO: Fixed speed setpoint 1
Vector 300
300 rpm
Vector
p1002
CO: Fixed speed setpoint 2
Vector 600
600 rpm
Vector
p1003
CO: Fixed speed setpoint 3
Vector 1500
1500 rpm
Vector
p1083
CO: Speed limit in positive direction
of rotation
Vector 6000
6000 rpm
Vector
p1086
CO: Speed limit in negative direction
of rotation
Vector -6000
-6000 rpm
Vector
p1115
Ramp-function generator selection
Vector 1
Extended ramp-function generator
Vector
p1120
Ramp-function generator ramp-up
time
Vector 20
20 s
Vector
p1121
Ramp-function generator ramp-down
time
Vector 30
30 s
Vector
p1135
OFF3 ramp-down time
Vector 10
10 s
Vector
p1200
Flying restart operating mode
Vector 0
Flying restart not active
Vector
p1208.0
BI: WEA infeed fault
Vector r2139.3
Fault active
A_INF
p1208.1
BI: WEA infeed supply break
Vector r0863.2
Drive link - infeed supply break
A_INF
p1240
Vdc controller configuration
Vector 0
Disable Vdc-max controller
Vector
p1254
Vdc controller automatic ON level
detection
Vector 1
Automatic detection enabled
Vector
Содержание SINAMICS S150 NEMA
Страница 1: ......
Страница 2: ......
Страница 20: ...Table of contents Enclosed Drives 18 Operating Instructions 12 2018 A5E36652151A ...
Страница 42: ...Device overview 2 5 Rating plate Enclosed Drives 40 Operating Instructions 12 2018 A5E36652151A ...
Страница 200: ...Electrical installation 4 9 Additional connections Enclosed Drives 198 Operating Instructions 12 2018 A5E36652151A ...
Страница 500: ...Output terminals 8 3 Digital outputs Enclosed Drives 498 Operating Instructions 12 2018 A5E36652151A ...
Страница 828: ...Technical specifications 12 3 Technical specifications Enclosed Drives 826 Operating Instructions 12 2018 A5E36652151A ...