Operation
6.5 Setpoint sources
Enclosed Drives
288
Operating Instructions, 12/2018, A5E36652151A
F3505 – Fault: "Analog input wire break"
This fault occurs when analog input type (p4056) is set to 3 (4 ... 20 mA with wire break
monitoring), and the input current of 2 mA has been undershot.
The fault value can be used to determine the analog input in question.
Component number
4: Module -A60 / -X65
5: Module -A61 (optional)
0: Analog input 0: -X521:1/2
1: Analog input 1: -X521:3/4
6.5.2
Motorized potentiometer
Description
The digital motorized potentiometer enables you to set speeds remotely using switching
signals (+/- keys). It is activated via terminals or fieldbus. As long as a logical 1 is present at
signal input "MOP raise" (setpoint higher), the internal numerator integrates the setpoint. You
can set the integration time (time taken for the setpoint to increase) using parameter p1047.
In the same way, you can decrease the setpoint using signal input "MOP lower". The
deceleration ramp can be set using parameter p1048.
Configuration parameter p1030.0 = 1 (default setting = 0) enables non-volatile storage of the
current motorized potentiometer value when powering down the drive unit. When powering-
up the drive unit, the starting (initial) value of the motorized potentiometer is set to the last,
actual value that was present when the drive unit was powered-down.
Precondition
The default setting for the motorized potentiometer was chosen during commissioning:
•
STARTER (p1000):
"Motorized potentiometer"
•
AOP30 (p1000):
"3: Motorized potentiometer"
Содержание SINAMICS S150 NEMA
Страница 1: ......
Страница 2: ......
Страница 20: ...Table of contents Enclosed Drives 18 Operating Instructions 12 2018 A5E36652151A ...
Страница 42: ...Device overview 2 5 Rating plate Enclosed Drives 40 Operating Instructions 12 2018 A5E36652151A ...
Страница 200: ...Electrical installation 4 9 Additional connections Enclosed Drives 198 Operating Instructions 12 2018 A5E36652151A ...
Страница 500: ...Output terminals 8 3 Digital outputs Enclosed Drives 498 Operating Instructions 12 2018 A5E36652151A ...
Страница 828: ...Technical specifications 12 3 Technical specifications Enclosed Drives 826 Operating Instructions 12 2018 A5E36652151A ...
Страница 861: ......
Страница 862: ......