![Siemens SINAMICS S150 NEMA Скачать руководство пользователя страница 729](http://html.mh-extra.com/html/siemens/sinamics-s150-nema/sinamics-s150-nema_operating-instructions-manual_381570729.webp)
Diagnostics / faults and alarms
10.2 Diagnostics
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
727
Table 10- 14 Description of the OPT LED on the Control Unit
LED
Color
State
Description
OPT
---
OFF
Electronics power supply is missing or outside permissible tolerance
range.
The CBE20 is defective or not inserted.
Green
Continuous light
CBE20 is ready and cyclic communication is taking place.
0.5 Hz flashing light
CBE20 is ready but cyclic communication is not running.
Possible causes:
- Communication is being established.
-At least one fault is present.
Red
Continuous light
Cyclic communication via PROFINET has not yet been established.
However, acyclic communication is possible. SINAMICS is waiting for a
parameterization/configuration telegram.
0.5 Hz flashing light
The firmware download to the CBE20 has failed.
Possible causes:
- The memory card of the Control Unit is faulty.
- The CBE20 is out of order.
The CBE20 cannot be used in this state.
2 Hz flashing light
Communication between the Control Unit and the CBE20 is faulty.
Possible causes:
- The CBE20 was removed following power-up.
- The CBE20 is defective.
Orange
0.5 Hz flashing light
Firmware is being updated.
TM150 - Terminal Module (-A151)
Table 10- 15 Description of the LEDs on the TM150
LED
Color
State
Description
READY -
OFF
The electronic power supply is missing or lies outside the permissible
tolerance range.
Green
Continuous light
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
Orange
Continuous light
DRIVE-CLiQ communication is being established.
Red
Continuous light
This component has at least one fault.
Remark:
The LED is activated irrespective of whether the corresponding
messages have been reconfigured.
Green/red
Flashing light 0.5 Hz Firmware is being downloaded.
Flashing light 2 Hz
Firmware download is complete. Waiting for POWER ON.
Green / orange
or
red / orange
Flashing light 2 Hz
Detection of the components via LED is activated (p0154).
Remark:
Both options depend on the LED status when module recognition is
activated via p0154 = 1.
Содержание SINAMICS S150 NEMA
Страница 1: ......
Страница 2: ......
Страница 20: ...Table of contents Enclosed Drives 18 Operating Instructions 12 2018 A5E36652151A ...
Страница 42: ...Device overview 2 5 Rating plate Enclosed Drives 40 Operating Instructions 12 2018 A5E36652151A ...
Страница 200: ...Electrical installation 4 9 Additional connections Enclosed Drives 198 Operating Instructions 12 2018 A5E36652151A ...
Страница 500: ...Output terminals 8 3 Digital outputs Enclosed Drives 498 Operating Instructions 12 2018 A5E36652151A ...
Страница 828: ...Technical specifications 12 3 Technical specifications Enclosed Drives 826 Operating Instructions 12 2018 A5E36652151A ...
Страница 861: ......
Страница 862: ......