Setpoint channel and closed-loop control
7.4 Vector speed/torque control with/without an encoder
Enclosed Drives
488
Operating Instructions, 12/2018, A5E36652151A
Supplementary conditions
●
Maximum speed or maximum torque depend on the converter output voltage available
and the back EMF of the motor (calculation specifications: EMF must not exceed
U
rated, converter
).
●
Calculating the maximum speed:
●
Depending on the terminal voltage and load cycle, the maximum torque can be taken
from the motor data sheets / configuration instructions.
●
One of the following motor encoders must be deployed for operation with an encoder:
–
SMC10 (option K46): all resolvers that can be connected
–
SMC20 (option K48): SIN/COS encoders with C/D track, EnDat encoders
–
SMC30 (option K50): HTL/TTL encoders with zero mark.
●
No thermal model is available for the closed-loop control of a permanent-magnet
synchronous motor. The motor can only be protected against overheating by using
temperature sensors (PTC, KTY, PT1000). To achieve a high level of torque accuracy,
we recommend a temperature sensor (KTY, PT1000) to measure the motor temperature.
Commissioning
The following sequence is recommended for commissioning:
●
Configure the drive
When the drive is being commissioned using STARTER or the AOP30 operator panel,
the permanent-magnet synchronous motor must be selected. The motor data specified in
the table below must then be entered. Finally, the motor identification routine and speed
optimization (p1900) are activated. Encoder adjustment is activated automatically
together with the motor identification routine.
●
Motor identification (standstill measurement, p1910)
●
Encoder adjustment (p1990) (not for operation without encoder)
Motor Modules with field-oriented closed-loop control specify the current on permanent-
magnet synchronous motors with regard to the magnetic flux in the motor. To this end,
the motor encoder must provide information about the position of the rotor.
Note
Encoder adjustment
During initial commissioning and when the encoder is replaced, the encoder must be
adjusted (p1990).
●
Speed controller optimization (rotary measurement, p1960)
Содержание SINAMICS S150 NEMA
Страница 1: ......
Страница 2: ......
Страница 20: ...Table of contents Enclosed Drives 18 Operating Instructions 12 2018 A5E36652151A ...
Страница 42: ...Device overview 2 5 Rating plate Enclosed Drives 40 Operating Instructions 12 2018 A5E36652151A ...
Страница 200: ...Electrical installation 4 9 Additional connections Enclosed Drives 198 Operating Instructions 12 2018 A5E36652151A ...
Страница 500: ...Output terminals 8 3 Digital outputs Enclosed Drives 498 Operating Instructions 12 2018 A5E36652151A ...
Страница 828: ...Technical specifications 12 3 Technical specifications Enclosed Drives 826 Operating Instructions 12 2018 A5E36652151A ...
Страница 861: ......
Страница 862: ......