![Siemens SINAMICS S150 NEMA Скачать руководство пользователя страница 442](http://html.mh-extra.com/html/siemens/sinamics-s150-nema/sinamics-s150-nema_operating-instructions-manual_381570442.webp)
Setpoint channel and closed-loop control
7.2 Setpoint channel
Enclosed Drives
440
Operating Instructions, 12/2018, A5E36652151A
Function diagrams
At certain points in this section, reference is made to function diagrams. These can be found
on the customer DVD in the "SINAMICS S120/S150 List Manual", which provides
experienced users with detailed descriptions of all the functions.
7.2
Setpoint channel
7.2.1
Setpoint addition
Description
The supplementary setpoint can be used to enter correction values from higher-level closed-
loop controls. This can be implemented using the summing point of the main/supplementary
setpoint in the setpoint channel. Both variables are imported simultaneously via two separate
or one setpoint source and added in the setpoint channel.
Function diagram
FD 3030
Main/added setpoint, setpoint scaling, jogging
Parameters
•
p1070
Main setpoint
•
p1071
Main setpoint scaling
•
r1073
Main setpoint effective
•
p1075
Supplementary setpoint
•
p1076
Supplementary setpoint scaling
•
r1077
Supplementary setpoint effective
•
r1078
Total setpoint effective
Содержание SINAMICS S150 NEMA
Страница 1: ......
Страница 2: ......
Страница 20: ...Table of contents Enclosed Drives 18 Operating Instructions 12 2018 A5E36652151A ...
Страница 42: ...Device overview 2 5 Rating plate Enclosed Drives 40 Operating Instructions 12 2018 A5E36652151A ...
Страница 200: ...Electrical installation 4 9 Additional connections Enclosed Drives 198 Operating Instructions 12 2018 A5E36652151A ...
Страница 500: ...Output terminals 8 3 Digital outputs Enclosed Drives 498 Operating Instructions 12 2018 A5E36652151A ...
Страница 828: ...Technical specifications 12 3 Technical specifications Enclosed Drives 826 Operating Instructions 12 2018 A5E36652151A ...
Страница 861: ......
Страница 862: ......