Appendix
A.3 Parameter macros
Enclosed Drives
838
Operating Instructions, 12/2018, A5E36652151A
Sink
Source
Parameter
Description
DO Parameter
Description
DO
p1280
Vdc controller configuration (V/f)
Vector 0
Disable Vdc-max controller
Vector
p1300
Open-loop/closed-loop control
operating mode
Vector 20
Encoderless speed control
Vector
p1911
Number of phases to be identified
Vector 1
1 phase
Vector
p2051[0]
CI: PROFIBUS PZD send word
Vector r2089[0]
ZSW1
Vector
p2051[1]
CI: PROFIBUS PZD send word
Vector r0063[0]
n-act unsmoothed
Vector
p2051[2]
CI: PROFIBUS PZD send word
Vector r0068[0]
I-act unsmoothed
Vector
p2051[3]
CI: PROFIBUS PZD send word
Vector r0080[0]
M-act unsmoothed
Vector
p2051[4]
CI: PROFIBUS PZD send word
Vector r0082[0]
P-act unsmoothed
Vector
p2051[5]
CI: PROFIBUS PZD send word
Vector r2131
FAULT
Vector
p2080[0]
BI: PROFIBUS send status word 1
Vector r0899.0
Ready for switching on
Vector
p2080[1]
BI: PROFIBUS send status word 1
Vector r0899.1
Ready for operation
Vector
p2080[2]
BI: PROFIBUS send status word 1
Vector r0899.2
Operation
Vector
p2080[3]
BI: PROFIBUS send status word 1
Vector r2139.3
Fault
Vector
p2080[4]
BI: PROFIBUS send status word 1
Vector r0899.4
No OFF2
Vector
p2080[5]
BI: PROFIBUS send status word 1
Vector r0899.5
No OFF3
Vector
p2080[6]
BI: PROFIBUS send status word 1
Vector r0899.6
Switching on inhibited
Vector
p2080[7]
BI: PROFIBUS send status word 1
Vector r2139.7
Alarm active
Vector
p2080[8]
BI: PROFIBUS send status word 1
Vector r2197.7
No setpoint/actual value deviation
Vector
p2080[9]
BI: PROFIBUS send status word 1
Vector r0899.9
Control request
Vector
p2080[10]
BI: PROFIBUS send status word 1
Vector r2199.1
Comparison value reached
Vector
p2080[11]
BI: PROFIBUS send status word 1
Vector r1407.7
M/I/P limiting not active
Vector
p2080[12]
BI: PROFIBUS send status word 1
Vector 0
Vector
p2080[13]
BI: PROFIBUS send status word 1
Vector r2129.14
No alarm for motor overtemperature Vector
p2080[14]
BI: PROFIBUS send status word 1
Vector r2197.3
Clockwise
Vector
p2080[15]
BI: PROFIBUS send status word 1
Vector r2129.15
No Therm. alarm Power unit
overload
Vector
p2088
PROFIBUS Invert status word
Vector B800h
Vector
p2128[14]
Select fault/alarm code for trigger
Vector 7910
A7910: Alarm, motor
overtemperature
Vector
p2128[15]
Select fault/alarm code for trigger
Vector 5000
A5000: Therm. alarm Power unit
overload
Vector
p2153
Time constant revolutions actual
value filter
Vector 20
20 ms
Vector
p0840[0]
ON/OFF 1
A_INF r0863.1
Energize line contactor
Vector
p2105
BI: 3. Acknowledge faults
A_INF r1214.3
Automatic restart status – set
acknowledgement command
Vector
p1207
BI: WEA link, following DO
A_INF r1214.2
Automatic restart status – restart
active
Vector
p4053[0]
TM31 analog inputs, smoothing time
constant
TM31 0
0 ms
TM31
p4053[1]
TM31 analog inputs, smoothing time
constant
TM31 0
0 ms
TM31
Содержание SINAMICS S150 NEMA
Страница 1: ......
Страница 2: ......
Страница 20: ...Table of contents Enclosed Drives 18 Operating Instructions 12 2018 A5E36652151A ...
Страница 42: ...Device overview 2 5 Rating plate Enclosed Drives 40 Operating Instructions 12 2018 A5E36652151A ...
Страница 200: ...Electrical installation 4 9 Additional connections Enclosed Drives 198 Operating Instructions 12 2018 A5E36652151A ...
Страница 500: ...Output terminals 8 3 Digital outputs Enclosed Drives 498 Operating Instructions 12 2018 A5E36652151A ...
Страница 828: ...Technical specifications 12 3 Technical specifications Enclosed Drives 826 Operating Instructions 12 2018 A5E36652151A ...
Страница 861: ......
Страница 862: ......