Functions, monitoring and protective functions
9.4 Extended functions
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
627
Commissioning
The "extended monitoring functions" function module can be activated by running the
commissioning wizard. Parameter r0108.17 indicates whether it has been activated.
Function diagrams
FD 8010
Speed messages 1
FP 8011
Speed messages 2
FD 8013
Load monitoring
Parameters
•
p2150
Hysteresis speed 3
•
p2151
CI: Speed setpoint for messages
•
p2161
Speed threshold 3
•
p2181
Load monitoring, response
•
p2182
Load monitoring, speed threshold 1
•
p2183
Load monitoring, speed threshold 2
•
p2184
Load monitoring, speed threshold 3
•
p2185
Load monitoring, speed threshold 1 upper
•
...
•
p2190
Load monitoring, speed threshold 3 lower
•
p2192
Load monitoring, delay time
•
r2198.4 |n_set|
≤
p2161
•
r2198.5 n_set > 0
•
r2198.11 Load monitoring displays alarm
•
r2198.12 Load monitoring displays fault
Содержание SINAMICS S150 NEMA
Страница 1: ......
Страница 2: ......
Страница 20: ...Table of contents Enclosed Drives 18 Operating Instructions 12 2018 A5E36652151A ...
Страница 42: ...Device overview 2 5 Rating plate Enclosed Drives 40 Operating Instructions 12 2018 A5E36652151A ...
Страница 200: ...Electrical installation 4 9 Additional connections Enclosed Drives 198 Operating Instructions 12 2018 A5E36652151A ...
Страница 500: ...Output terminals 8 3 Digital outputs Enclosed Drives 498 Operating Instructions 12 2018 A5E36652151A ...
Страница 828: ...Technical specifications 12 3 Technical specifications Enclosed Drives 826 Operating Instructions 12 2018 A5E36652151A ...
Страница 861: ......
Страница 862: ......