Electrical installation
4.9 Additional connections
Enclosed Drives
120
Operating Instructions, 12/2018, A5E36652151A
Article no.
6SL3710- 7LE37-5AU3
7LE41-0AU3
SCCR (short circuit current rating)
according to UL508A File no.
E83449
8)
kA
65
84
Minimum short-circuit current
9)
A
12000
2500
1)
Rated output of a typical 6-pole standard induction motor based on I
L
or I
H
at 400 V 3 AC 50 Hz.
2)
Shaft output of the matching motor based on the current according to NEC table 430-250.
3)
The currents are based on a line power factor of cos
φ
= 1.
4)
The base-load current I
L
is based on a duty cycle of 110% for 60 s or 150% for 10 s with a duty cycle duration of 300 s
(see "Overload capability").
5)
The base-load current I
H
is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s
(see "Overload capability").
6)
The current values given here are based on the rated output current.
7)
The SCCR value of the cabinet unit is based on the fuses listed. Substitutes are not permitted.
8)
In conjunction with the specified fuses or circuit breakers.
9)
Minimum current required for reliable triggering of the protective devices.
10)
Current for unit rating
The possible output current of the inverter is specified in brackets.
11)
Stripped lengths of the power cables: front 1" (25.4 mm), rear 2" (50.8 mm).
Tightening torque: 375 lb.in. (42.4 Nm).
4.9.2
dv/dt filter plus Voltage Peak Limiter (option L10)
Description
The dv/dt filter plus Voltage Peak Limiter comprises two components: the dv/dt reactor and
the Voltage Peak Limiter , which cuts off the voltage peaks and returns the energy to the DC
link.
The dv/dt filters plus Voltage Peak Limiter must be used for motors for which the proof
voltage of the insulation system is unknown or insufficient. Standard motors of the 1LA5,
1LA6 and 1LA8 series only require them at supply voltages > 500 V +10%.
The dv/dt filter plus Voltage Peak Limiter limits the voltage gradient to values < 500 V/µs and
the typical transients to the values below (with motor cable lengths of < 150 m):
●
< 1000 V at U
line
< 575 V
●
< 1250 V at 660 V < U
line
< 690 V.
Depending on the converter power, option L10 can be accommodated in the converter
cabinet unit, or an additional cabinet with a width 15.8" (400 mm) or 23.6" (600 mm) is
required.
Содержание SINAMICS S150 NEMA
Страница 1: ......
Страница 2: ......
Страница 20: ...Table of contents Enclosed Drives 18 Operating Instructions 12 2018 A5E36652151A ...
Страница 42: ...Device overview 2 5 Rating plate Enclosed Drives 40 Operating Instructions 12 2018 A5E36652151A ...
Страница 200: ...Electrical installation 4 9 Additional connections Enclosed Drives 198 Operating Instructions 12 2018 A5E36652151A ...
Страница 500: ...Output terminals 8 3 Digital outputs Enclosed Drives 498 Operating Instructions 12 2018 A5E36652151A ...
Страница 828: ...Technical specifications 12 3 Technical specifications Enclosed Drives 826 Operating Instructions 12 2018 A5E36652151A ...
Страница 861: ......
Страница 862: ......