Infeed
2.4 Line contactor control
Drive functions
58
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
Commissioning steps:
1.
Connect the line contactor control contact to DI/DO 8
Note
The current-carrying capacity of the digital output must be observed (see SINAMICS
S120 Control Units and Supplementary System Components Manual). A contactor relay
may be required!
2.
Parameterize DI/DO 8 as output (p0728.8 = 1).
3.
Assign parameter p0738 the control signal for the line contactor r0863.1
4.
Connect the line contactor feedback contact to DI/DO 9.
5.
Assign p0860 an inverted input signal r0723.9.
6.
Enter the monitoring time for the line contactor (100 ms) in p0861.
Function diagrams (see SINAMICS S120/S150 List Manual)
•
8938
Active Infeed - Missing enables, line contactor control
Overview of important parameters (see SINAMICS S120/S150 List Manual)
•
p0860
BI: Line contactor, feedback signal
•
r0863.0...2
CO/BO: Drive coupling status word / control word
•
p0867
Power section main contactor hold time after OFF1
•
p0869
Configuration sequence control
Содержание SINAMICS S120
Страница 1: ......
Страница 2: ......
Страница 24: ...Contents Drive functions 24 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 202: ...Servo control 4 21 Voltage precontrol Drive functions 202 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 296: ...Vector control 5 23 Asynchronous pulse frequency Drive functions 296 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 312: ...V f control vector control 6 5 Vdc control Drive functions 312 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 932: ......
Страница 1044: ...Appendix A 2 Documentation overview Drive functions 1044 Function Manual 11 2017 6SL3097 4AB00 0BP5 A 2 Documentation overview ...
Страница 1082: ...Appendix A 7 Functions of SINAMICS S120 Combi Drive functions 1082 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 1094: ......