Infeed
2.4 Line contactor control
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
57
2.4
Line contactor control
This function can be used to control an external line contactor. Opening and closing the line
contactor can be monitored by evaluating the feedback contact in the line contactor.
The line contactor can be controlled via r0863.1 with the following drive objects:
●
for the INFEED drive object
●
for the SERVO and VECTOR drive objects
Note
Further information on the line connection can be found in the manuals:
Example of commissioning line contactor control
Assumption:
●
Line contactor control via a digital output of the Control Unit (DI/DO 8)
●
Line contactor feedback via a digital input of the Control Unit (DI/DO 9)
●
Line contactor switching time less than 100 ms
Figure 2-10 Line contactor control
Содержание SINAMICS S120
Страница 1: ......
Страница 2: ......
Страница 24: ...Contents Drive functions 24 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 202: ...Servo control 4 21 Voltage precontrol Drive functions 202 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 296: ...Vector control 5 23 Asynchronous pulse frequency Drive functions 296 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 312: ...V f control vector control 6 5 Vdc control Drive functions 312 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 932: ......
Страница 1044: ...Appendix A 2 Documentation overview Drive functions 1044 Function Manual 11 2017 6SL3097 4AB00 0BP5 A 2 Documentation overview ...
Страница 1082: ...Appendix A 7 Functions of SINAMICS S120 Combi Drive functions 1082 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 1094: ......