Vector control
5.22 Bypass
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
285
A reactor is used to de-couple the drive converter from the line supply - the uk value for the
reactor is 10% +/
- 2%.
Figure 5-26 Circuit example: Bypass with synchronization with overlap
Note
As a result of the overlap, when synchronizing back to the converter, the DC link voltage can
increase; in the worst case scenario this can result in a fault trip. It is possible to activate an
overvoltage protection function, which, when a Vdc max threshold r1242 is reached, the
pulses are inhibited; as a consequence, the DC link voltage stops increasing. When the
pulses are inhibited, the motor coasts down, which is why it must be restarted on-the-fly. As
a consequence, overvoltage protection is only active if the "Flying restart" function was
activated (p1200 = 1).
Activation
The bypass function with synchronization with overlap (p1260 = 1) can only be activated
using a control signal. Activation using a speed threshold is not possible.
Содержание SINAMICS S120
Страница 1: ......
Страница 2: ......
Страница 24: ...Contents Drive functions 24 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 202: ...Servo control 4 21 Voltage precontrol Drive functions 202 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 296: ...Vector control 5 23 Asynchronous pulse frequency Drive functions 296 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 312: ...V f control vector control 6 5 Vdc control Drive functions 312 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 932: ......
Страница 1044: ...Appendix A 2 Documentation overview Drive functions 1044 Function Manual 11 2017 6SL3097 4AB00 0BP5 A 2 Documentation overview ...
Страница 1082: ...Appendix A 7 Functions of SINAMICS S120 Combi Drive functions 1082 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 1094: ......