8.10.1
Applications of parallel connections
Power units can be connected in parallel (infeeds) in the following cases:
●
6-pulse circuit
The modules connected in parallel are supplied from a two-winding transformer.
●
12-pulse circuit
The modules connected in parallel are supplied via a three-winding transformer, whose
secondary windings supply voltages with a phase shift of 30°.
The following diagram is an overview of the module variants discussed in this section for
inclusion in power unit parallel connections.
Figure 8-25 Parallel connection of power units - overview
Note
Additional information on parallel power unit connections, particularly with regard to their
configuration, can be found in the "SINAMICS Low Voltage Configuration Manual
http://www.automation.siemens.com/mcms/infocenter/dokumentencenter/ld/Documentsu20
Catalogs/lv-umrichter/sinamics-engineering-manual-lv-en.pdf
)".
Infeed concepts - parallel (one CU) and redundant parallel (two CUs)
Some applications require redundant infeeds for a DC line-up. This requirement can be
fulfilled through the implementation of multiple, independent infeeds which are connected in
parallel to the DC line-up. Depending on how the drive is dimensioned, the DC line-up can
continue operating at between 50% to 100% output when one infeed fails. With the
redundant variant of the infeed parallel connection, each infeed is controlled by a separate
Control Unit and is thus completely independent. With the non-redundant variant, a single
Control Unit generally controls all parallel-connected power units which then, from a practical
viewpoint, function like a single, high-output infeed.
Содержание SINAMICS S120
Страница 1: ......
Страница 2: ......
Страница 24: ...Contents Drive functions 24 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 202: ...Servo control 4 21 Voltage precontrol Drive functions 202 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 296: ...Vector control 5 23 Asynchronous pulse frequency Drive functions 296 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 312: ...V f control vector control 6 5 Vdc control Drive functions 312 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 932: ......
Страница 1044: ...Appendix A 2 Documentation overview Drive functions 1044 Function Manual 11 2017 6SL3097 4AB00 0BP5 A 2 Documentation overview ...
Страница 1082: ...Appendix A 7 Functions of SINAMICS S120 Combi Drive functions 1082 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 1094: ......