Basic functions
7.25 Upgrade the firmware and project
Drive functions
410
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
Update
This operation can take several minutes. This is indicated by the RDY-LED on the
corresponding components flashing green/red and the Control Unit RDY-LED flashing
orange at 0.5 Hz.
Parameter p7827 indicates the progress.
The update has been completed if the RDY-LED on the Control Unit stops to flash at 0.5 Hz.
Once the update process has been completed, the RDY-LED of the respective component
goes into a steady light condition, for which the upgrade has been completed and the new
firmware has been activated. For the components for which the RDY LED flashes green/red
at 2 Hz you must perform a POWER ON to activate the new firmware.
Note
When activating the new firmware, it is possible that a component interrupts cyclic
communication. Communication problems will then occur that you must acknowledge.
For individual components, STARTER dialogs ("Drive Unit" -> "Configuration" -> "Version
Overview") can be used to read the firmware version or start a firmware upgrade manually
for specific components. The versions of the DRIVE-CLiQ components and that of the
Control Unit can also differ. Information can be found in the version overview.
Note
DRIVE-CLiQ components with higher firmware releases are downwards compatible and also
operate with DRIVE-CLiQ components that have lower firmware releases.
Note
Upgrade for SINAMICS S120 chassis
Upgrading S120 chassis devices is more complex and involves more settings than for
booksize devices. You can find a detailed description of the procedure when upgrading
chassis devices at the following SIEMENS internet site
Upgrading S120 chassis devices
https://support.industry.siemens.com/cs/ww/en/view/60494864
7.25.2
Updating the firmware via the Web server
7.25.2.1
Overview
You can update the data on your memory card directly via an Internet connection with the
aid of the network connection. You can use this to transfer configuration data and the latest
firmware to the memory card.
For safety reasons, the current data is not directly overwritten when you update the data on
the memory card. There is a double data storage via a backup partition. In this way,
damaged data can be restored automatically after an automatic test in the event of a fault.
Содержание SINAMICS S120
Страница 1: ......
Страница 2: ......
Страница 24: ...Contents Drive functions 24 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 202: ...Servo control 4 21 Voltage precontrol Drive functions 202 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 296: ...Vector control 5 23 Asynchronous pulse frequency Drive functions 296 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 312: ...V f control vector control 6 5 Vdc control Drive functions 312 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 932: ......
Страница 1044: ...Appendix A 2 Documentation overview Drive functions 1044 Function Manual 11 2017 6SL3097 4AB00 0BP5 A 2 Documentation overview ...
Страница 1082: ...Appendix A 7 Functions of SINAMICS S120 Combi Drive functions 1082 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 1094: ......