Servo control
4.21 Voltage precontrol
Drive functions
200
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
7.
Restore the P gain (p1715) and integral time (p1717) of the current controller back to the
original values.
8.
Again measure a current controller setpoint step.
Figure 4-34 Example: after optimization/tuning
In most cases, the voltage precontrol is correctly set after the eddy current compensation
(see example). If required, you can correct again using p1734.
Legend for the measurement diagrams
Torque-generating current setpoint
Torque-generating current setpoint unsmoothed
Quadrature-axis voltage setpoint