Communication
11.3 Communication via PROFINET IO
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
817
Comparison between RT and IRT
Table 11- 12 Comparison between RT and IRT
RT
IRT "high flexibility"
IRT "high performance"
Transfer mode
Switching based on the MAC
address; prioritization of the
RT telegrams possible using
Ethernet-Prio (VLAN tag).
Switching using the MAC
address;
bandwidth reservation by
reserving an IRT "high flexi-
bility" interval in which only
IRT "high flexibility" frames
are transferred but, for ex-
ample, no TCP/IP frames.
Path-based switching ac-
cording to a topology-based
plan; no transmission of
TCP/IP frames and IRT "high
flexibility" frames in the IRT
"high performance" interval.
Isochronous application
in the IO controller
No
No
Yes
Determinism
Variance of the transmission
duration by started TCP/IP
telegrams.
Guaranteed transmission of
the IRT "high flexibility" tele-
grams in the current cycle by
the reserved bandwidth.
Exactly planned transfer;
times for transmission and
receiving are guaranteed for
any topologies.
Reload the network configu-
ration after a change
Not relevant
Only when the size of the
IRT "high flexibility" interval
needs to be modified (reser-
vation of position is possi-
ble).
Always when the topology or
the communications relation-
ships change.
Maximum switching depth
(number of switches in one
line)
10 at 1 ms
61
64
For possible send cycles, see subitem "Send cycles and update cycles for RT classes" in table "Adjustable send cycles
and update cycles"
Set the RT class
The RT class is set by means of the properties of the controller interface of the IO controller.
If RT class IRT "high performance" is set, it is not possible to operate any IRT "high
flexibility" devices on the IO controller and vice versa. IO devices with RT can always be
operated, regardless of the IRT class setting.
You can set the RT class in the HW Config for the associated PROFINET device.
1.
In HW Config, double-click item PROFINET interface in the module.
The "Properties" dialog box opens.
2.
Select the RT class under RT class on the "Synchronization" tab.
3.
Once you have selected "IRT", you can also choose between option "high flexibility" and
"high performance".
4.
Confirm with "OK".
Содержание SINAMICS S120
Страница 1: ......
Страница 2: ......
Страница 24: ...Contents Drive functions 24 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 202: ...Servo control 4 21 Voltage precontrol Drive functions 202 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 296: ...Vector control 5 23 Asynchronous pulse frequency Drive functions 296 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 312: ...V f control vector control 6 5 Vdc control Drive functions 312 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 932: ......
Страница 1044: ...Appendix A 2 Documentation overview Drive functions 1044 Function Manual 11 2017 6SL3097 4AB00 0BP5 A 2 Documentation overview ...
Страница 1082: ...Appendix A 7 Functions of SINAMICS S120 Combi Drive functions 1082 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 1094: ......