Basic functions
7.13 Motor Module as a Braking Module
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
351
7.13.2
Configuring resistors
Rules and values
●
Under no circumstances may the resistance values for the peak braking power, which are
listed in this table, be fallen below!
●
The resistance values apply for each of the three resistors in a star connection in the cold
state.
●
Each braking resistor absorbs 1/3 of the total braking power. It is imperative that you take
into account the power rating of the resistors.
●
For a delta connection, multiply the braking resistance value by a factor of 3.
●
The tables apply for all Motor Modules of the "chassis" format (liquid or air cooling).
●
The cable lengths to the resistors must be at least 10 m.
●
At rated voltages of 380 V to 480 V,
Motor Modules with a type rating ≥ 250 kW are
permitted.
●
At rated voltages of 500 V to 690 V, all Motor Modules in the "chassis" format have been
released for use of this function.
You can enter the resistance value in a star connection into parameter p1360. The default
setting of the resistance values is calculated from:
●
p1360 = p1362[0] /
(√(6)
·
r0207[0])
●
p1362[0] = Braking Module activation threshold according to the following table.
●
r0207[0...4] = rated current of the Motor Module
Table 7- 8
Resistance table 380 - 480 V supply voltage
Motor
Module
frame size
Rated volt-
age
Rated
current
Braking
current
U
DC link
chopper
threshold
Continu-
ous brak-
ing power
Peak
braking
power
Resistance at the
continuous brak-
ing power
Resistance at the
peak braking
power
[V]
[A]
[A]
[V]
[kW]
[kW]
[Ω]
[Ω]
G
400
490
450
667
368
551
0.605
0.403
480
490
450
774
427
640
0.702
0.466
H
400
605
545
667
445
668
0.500
0.333
480
605
545
774
517
775
0.580
0.387
H
400
745
680
667
555
833
0.400
0.267
480
745
680
774
645
967
0.465
0.310
H
400
840
800
667
654
980
0.340
0.277
480
840
800
774
758
1138
0.395
0.263
J
400
985
900
667
735
1103
0.303
0.202
480
985
900
774
853
1280
0.351
0.234
Содержание SINAMICS S120
Страница 1: ......
Страница 2: ......
Страница 24: ...Contents Drive functions 24 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 202: ...Servo control 4 21 Voltage precontrol Drive functions 202 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 296: ...Vector control 5 23 Asynchronous pulse frequency Drive functions 296 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 312: ...V f control vector control 6 5 Vdc control Drive functions 312 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 932: ......
Страница 1044: ...Appendix A 2 Documentation overview Drive functions 1044 Function Manual 11 2017 6SL3097 4AB00 0BP5 A 2 Documentation overview ...
Страница 1082: ...Appendix A 7 Functions of SINAMICS S120 Combi Drive functions 1082 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 1094: ......