9.5.7.3
Forming groups of temperature sensors
You can combine the temperature channels to form groups using parameter p4111[0...2].
For each group, the following calculated values are provided from the temperature actual
values (r4105[0...11]):
●
Maximum: r4112[0...2], (index 0,1,2 = group 0,1,2)
●
Minimum: r4113[0...2]
●
Average value: r4114[0...2]
Example:
The temperature actual value from channels 0, 3, 7, and 9 should be combined in group 1:
●
p4111[1].0 = 1
●
p4111[1].3 = 1
●
p4111[1].7 = 1
●
p4111[1].9 = 1
The calculated values from group 1 are available in the following parameters for
interconnection:
●
r4112[1] = maximum
●
r4113[1] = minimum
●
r4114[1] = average value
Note
Forming groups of temperature channels
Only form groups of continuously measuring temperature sensors. The switching
temperature sensors PTC and bimetallic NC contacts are only assigned two temperatures -
50° C and +250° C, depending on the state. Within a group with continuous temperature
actual values, the calculation of the maximum/minimum/average value temperature is
significantly falsified by taking into account switching temperature sensors.
9.5.7.4
Evaluating temperature channels
For each of the individual 12 temperature channels, an alarm threshold and a fault threshold
can be set in p4102[0...23]. The even parameter indices contain the alarm threshold and the
uneven parameter indices, the fault threshold. The temperature thresholds can be set
between -
99°C and +251°C for each channel.
If the evaluation of the temperature actual value from p4105[0...11] exceeds the alarm
threshold set in p4102[0...23], then an alarm is output at r4104.0...23. Timer p4103[0...11] is
started at the same time.
If, after the timer has expired, the temperature actual value is still above the alarm threshold,
then an appropriate fault is output. This fault can be acknowledged as soon as the
temperature actual value is again below the alarm threshold.
Содержание SINAMICS S120
Страница 1: ......
Страница 2: ......
Страница 24: ...Contents Drive functions 24 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 202: ...Servo control 4 21 Voltage precontrol Drive functions 202 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 296: ...Vector control 5 23 Asynchronous pulse frequency Drive functions 296 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 312: ...V f control vector control 6 5 Vdc control Drive functions 312 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 932: ......
Страница 1044: ...Appendix A 2 Documentation overview Drive functions 1044 Function Manual 11 2017 6SL3097 4AB00 0BP5 A 2 Documentation overview ...
Страница 1082: ...Appendix A 7 Functions of SINAMICS S120 Combi Drive functions 1082 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 1094: ......