Function modules
8.10 Parallel connection of power units
Drive functions
564
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
8.10.1.1
Parallel connection of Basic Line Modules
Features of Basic Line Modules:
●
The DC-link voltage is greater than the rms value of the line rated voltage by a factor of
1.35.
●
They are used in cases where regenerative feedback capability is not required.
●
If regenerative operating states occur in the drive line-up, Braking Modules that convert
the excess energy to heat in braking resistors must be used.
Basic Line Modules in chassis format are available for the following voltages and power
ratings:
Table 8- 9
Basic Line Modules
Line supply voltage
Rated power
380 to 480 V 3 phase AC
200 ... 710 kW
500 to 690 V 3-phase AC
250 ... 1100 kW
The following rules must be observed when connecting Basic Line Modules in parallel:
●
Up to four identical Basic Line Modules can be connected in parallel.
●
A common Control Unit must always be used to implement the parallel connection.
●
Special Line Connection Modules are available for the parallel connection.
●
With multiple infeeds, power must be supplied to the systems from a common infeed
point (i.e. the modules cannot be operated on different line supplies).
●
A current reduction (derating) of 7.5% must be taken into consideration, regardless of the
number of modules connected in parallel.
As Basic Line Modules have no current compensation control, the three-winding transformer,
power cabling and line reactors must meet the following requirements in order to provide a
balanced current:
●
Three-winding transformer must be symmetrical, recommended vector groups Dy5d0 or
Dy11d0.
●
Relative short-circuit voltage of three-winding transformer u
k
≥ 4%.
●
Difference between relative short-
circuit voltages of secondary windings Δu
k
≤ 5%.
●
Difference between no-
load voltages of secondary windings ΔU ≤ 0.5%.
●
Use of symmetrical power cabling between the transformer and the Basic Line Modules
(cables of identical type with the same cross-section and length)
●
Using line reactors that match the Basic Line Modules
Line reactors can be omitted if a double-tier transformer is used and only one Basic Line
Module is connected to each secondary winding of the transformer.
A double-tier transformer is generally the only means of meeting the requirements of a three-
winding transformer for this application. Line reactors must always be installed if other types
of three-winding transformer are used. Alternative solutions for obtaining a phase
displacement of 30°, such as two separate transformers with different vector groups, cannot
be used due to the inadmissibly high tolerances involved.
Содержание SINAMICS S120
Страница 1: ......
Страница 2: ......
Страница 24: ...Contents Drive functions 24 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 202: ...Servo control 4 21 Voltage precontrol Drive functions 202 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 296: ...Vector control 5 23 Asynchronous pulse frequency Drive functions 296 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 312: ...V f control vector control 6 5 Vdc control Drive functions 312 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 932: ......
Страница 1044: ...Appendix A 2 Documentation overview Drive functions 1044 Function Manual 11 2017 6SL3097 4AB00 0BP5 A 2 Documentation overview ...
Страница 1082: ...Appendix A 7 Functions of SINAMICS S120 Combi Drive functions 1082 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 1094: ......