Safety Integrated Basic Functions
10.5 Safe Stop 1 (SS1, time controlled)
Drive functions
686
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
Functional features of Safe Stop 1
SS1 is enabled by p9652 (delay time) ≠ 0.
●
Setting parameter p9652 has the following effect:
–
p9652 = 0
SS1 is not enabled. Only STO can be selected via TM54F, the onboard terminals
and/or PROFIsafe.
–
p9652 > 0
SS1 is enabled. Only SS1 can be selected via the onboard terminals; with PROFIsafe,
a selection of SS1 and STO is possible.
●
When SS1 is selected, the drive is braked along the OFF3 ramp (p1135) and STO/SBC is
automatically initiated after the delay time has expired (p9652).
After the function has been selected, the delay timer runs down - even if the function is
deselected during this time. In this case, after the delay time has expired, the STO/SBC
function is selected and then again deselected immediately.
Note
Setting the delay time
So that the drive is able to travel down the OFF3 ramp completely and any motor holding
brake present can be applied, before the pulses have been safely deleted, the delay time
should be set as follows:
•
Motor holding brake parameterized: Delay time p9652 ≥ p1135 + p1228
+ p1217
•
Motor holding brake not parameterized: Delay time p9652 ≥ p1135 + p1228
•
The setting of parameter p1135 must be oriented towards the actual braking capability
of the drive.
●
The timer (p9652) after whose expiration STO is activated, is implemented with two
channels, although deceleration along the OFF3 ramp is only one channel.
●
Effect on the "Speed setpoint limit effective" (r9733[0...2]):
For SS1 (≙
STOP B), a setpoint of 0 is specified in r9733[0...2].
Status of Safe Stop 1
The status of the "Safe Stop 1" (SS1) function is displayed using the parameters r9772,
r9872, r9773 and r9774.
As an alternative, the status of the function can be displayed using the configurable message
N01621 (configured using p2118 and p2119).
Содержание SINAMICS S120
Страница 1: ......
Страница 2: ......
Страница 24: ...Contents Drive functions 24 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 202: ...Servo control 4 21 Voltage precontrol Drive functions 202 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 296: ...Vector control 5 23 Asynchronous pulse frequency Drive functions 296 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 312: ...V f control vector control 6 5 Vdc control Drive functions 312 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 932: ......
Страница 1044: ...Appendix A 2 Documentation overview Drive functions 1044 Function Manual 11 2017 6SL3097 4AB00 0BP5 A 2 Documentation overview ...
Страница 1082: ...Appendix A 7 Functions of SINAMICS S120 Combi Drive functions 1082 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 1094: ......