Appendix
A.4 Parameterization using the BOP20
Drive functions
1062
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
A.4.4
Controlling the drive using the BOP20
When commissioning the drive, it can be controlled via the BOP20. A control word is
available on the Control Unit drive object (r0019) for this purpose, which can be
interconnected with the appropriate binector inputs of e.g. the drive.
The interconnections do not function if a standard PROFIdrive telegram was selected as its
interconnection cannot be disconnected.
Table A- 4
BOP20 control word
Bit (r0019)
Name
Example, interconnection parameters
0
ON / OFF (OFF1)
p0840
1
No coast down/coast down (OFF2)
p0844
2
No fast stop/fast stop (OFF3)
p0848
7
Acknowledge fault (0 -> 1)
p2102
13
Motorized potentiometer, raise
p1035
14
Motorized potentiometer, lower
p1036
Note
For simple commissioning, only bit 0 should be interconnected. When interconnecting
bits 0 ... 2, then the system is powered-down according to the following priority: OFF2,
OFF3, OFF1.
Содержание SINAMICS S120
Страница 1: ......
Страница 2: ......
Страница 24: ...Contents Drive functions 24 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 202: ...Servo control 4 21 Voltage precontrol Drive functions 202 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 296: ...Vector control 5 23 Asynchronous pulse frequency Drive functions 296 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 312: ...V f control vector control 6 5 Vdc control Drive functions 312 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 932: ......
Страница 1044: ...Appendix A 2 Documentation overview Drive functions 1044 Function Manual 11 2017 6SL3097 4AB00 0BP5 A 2 Documentation overview ...
Страница 1082: ...Appendix A 7 Functions of SINAMICS S120 Combi Drive functions 1082 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 1094: ......