Function modules
8.9 Master/slave function for Active Infeed
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
555
Explanations for the function diagrams
●
Current setpoint interconnection
Parameter p3570 is used to connect the setpoint for the closed-loop current control
(active current setpoint from the master). Using parameter p3513, which can be changed
in the "ready for operation" state, it is possible to switch between master (V
dc
control,
parameter p3513 = 0) and slave (current control, parameter p3513 = 1) from the higher-
level control system.
●
Selection of the current setpoint
The current setpoint can be selected by means of a control word (XCS) (p3572) using a
multiplexer with four inputs (X0 … X3) (p3571.0 … p3571.3). This means that the current
setpoint of the new master can be selected when the old master has failed.
●
Selection of the current distribution factor
To prevent a reduction in control dynamics of the DC-link voltage controller for non-
symmetrical loads, this current distribution factor must be updated immediately when an
infeed fails or is activated.
The current distribution factor is calculated from the number of active infeeds and their
rated data. The sum of the current distribution factors of all active infeeds must always
equal 100%.
The current distribution factor can be selected by means of a control word (XCS) (p3577)
using a multiplexer with six inputs (X0 ... X5) (p3576.0...5).
Alternatively, a new current distribution factor can be calculated in the higher-level
controller, sent via cyclic PROFIBUS PZD telegrams and interconnected directly to the
connector input "Infeed: additional current distribution factor" (p3579).
A further alternative is to update the current distribution factor via an acyclic PROFIBUS
parameter write order of p3516. This produces dead times however.
For alternatives without multiplexer, this can be used for a different function.
●
V
dc
control band
The V
dc
limits can be violated in master/slave operation if the DC-link load changes
abruptly (e.g. load surges or emergency stop). For this reason, the DC-link voltage is
monitored on the basis of a V
dc
control band. The V
dc
control band defines a specific
voltage range with hysteresis - set in parameter p3574.0/1 (upper/lower limit V
dc
voltage
band) and p3574.2/3 (hysteresis upper/lower voltage limit). A signal is generated if the
DC-link voltage leaves this voltage range. By evaluating this signal, the slave is changed
over from closed-loop current to closed-loop voltage control. When the DC-link voltage
returns to within the control band, the slave is switched back to closed-loop current
control. The V
dc
control operates permanently in "standby mode" so that it can be re-
activated when necessary.
Содержание SINAMICS S120
Страница 1: ......
Страница 2: ......
Страница 24: ...Contents Drive functions 24 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 202: ...Servo control 4 21 Voltage precontrol Drive functions 202 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 296: ...Vector control 5 23 Asynchronous pulse frequency Drive functions 296 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 312: ...V f control vector control 6 5 Vdc control Drive functions 312 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 932: ......
Страница 1044: ...Appendix A 2 Documentation overview Drive functions 1044 Function Manual 11 2017 6SL3097 4AB00 0BP5 A 2 Documentation overview ...
Страница 1082: ...Appendix A 7 Functions of SINAMICS S120 Combi Drive functions 1082 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 1094: ......