Communication
11.2 Communication via PROFIBUS DP
Drive functions
802
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
Diagnostics can be performed using the diagnostic parameters r2075 ("Receive PROFIBUS
diagnostics telegram offset PZD") and r2076 ("Send PROFIBUS diagnostics telegram offset
PZD"). The parameter r2074 ("PROFIBUS diagnostics, receive bus address PZD") displays
the DP address of the setpoint source of the respective PZD.
r2074 and r2075 enable the source of a slave-to-slave communication relationship to be
verified in the subscriber.
Note
The subscribers do not monitor the existence of an isochronous publisher sign-of-life.
Faults and alarms with PROFIBUS slave-to-slave communication
The alarm A01945 signals that the connection to a least one publisher of the drive device is
missing or has failed. Any interruption to the publisher is also reported by the fault F01946 at
the affected drive object. A failure of the publisher only impacts the respective drive objects.
More detailed information on the messages can be found in the SINAMICS S120/S150 List
Manual.
11.2.5
Messages via diagnostics channels
Messages can be displayed not only via the well-known commissioning tools (STARTER,
SCOUT). After the activation of a diagnostic function, the messages are also transferred to
the higher-level controller via the standardized PROFIdrive fault classes. The messages are
evaluated there or forwarded for convenient display to the corresponding user interfaces
(SIMATIC HMI, TIA Portal, etc.).
In this way, problems or faults can be located immediately regardless of the tool currently
being used, and then corrected immediately.
Also note the general information on the diagnostics channels in Section Diagnostics
Содержание SINAMICS S120
Страница 1: ......
Страница 2: ......
Страница 24: ...Contents Drive functions 24 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 202: ...Servo control 4 21 Voltage precontrol Drive functions 202 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 296: ...Vector control 5 23 Asynchronous pulse frequency Drive functions 296 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 312: ...V f control vector control 6 5 Vdc control Drive functions 312 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 932: ......
Страница 1044: ...Appendix A 2 Documentation overview Drive functions 1044 Function Manual 11 2017 6SL3097 4AB00 0BP5 A 2 Documentation overview ...
Страница 1082: ...Appendix A 7 Functions of SINAMICS S120 Combi Drive functions 1082 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 1094: ......