72/327
Building Technologies
Basic Documentation LMV5...
CC1P7550en
4 Burner control
22.05.2018
4.2.5 Auxiliary functions
4.2.5.1 Hours run counter
The LMV5 has an hour’s run counter for gas-fired and oil-fired operation.
The counters start from safety time 1 (phase 40) and are stopped at the end of
operation (when leaving the 6X phases).
The following counters are available and can be displayed using the AZL52 in the
Operation / HoursRun
menu; some of the settings can also be adjusted:
Parameter GasFiring
Operating hours for gas (adjustable)
OilStage1/Mod
Operating hours for oil stage 1 or modulating
(adjustable)
OilStage2
Operating hours for oil stage 2 (adjustable)
OilStage3
Operating hours for oil stage 3 (adjustable)
TotalHoursReset
Total operating hours (resettable)
TotalHours
Total operating hours (read only)
SystemOnPower
Operating hours when system is connected to
power (read only)
4.2.5.2 Start counter / startup counter
The LMV5 records the number of starts / startups and saves these permanently (via
mains voltage OFF).
The relevant start counters count up with each burner startup cycle (phase 20). This
also occurs if startup is subsequently aborted.
The following counters are available and can be displayed using the AZL52 in the
Operation / StartCounter
menu; some of the settings can also be adjusted:
Parameter GasStartCount
Number of startups for gas, start counter
(adjustable)
OilStartCount
Number of startups for oil, start counter
(adjustable)
TotalStartCountR
Total no. of startups, start counter (resettable)
TotalStartCount
Total no. of startups, start counter (read only)
4.2.5.3 End of life cycle function
The end of the life cycle of the LMV5 (switching cycles of the relays) is detected and
displayed on the AZL52.
The end of the life cycle is reached when the total startup counter
TotalStartCount
has
reached 250,000 starts.
This leads to the following message on the AZL52:
Startups > 250,000 maintenance
This means that the LMV5 has to be replaced, refer to chapter
Life cycle
.
This message can be hidden manually by pressing ESC.
If the message has been hidden, it will automatically appear again after an additional
10,000 starts.
Error and start prevention messages have priority over the end of lifecycle message.
4.2.5.4 Fuel meter
Refer to chapter
VSD module
.